Product Introduction
Technical Parameters
Unit
Parameters
Rated Voltage
kV
12
Rated Current
A
3150
Rated Power Frequency Withstand Voltage (1min)
kV
42/48
Rated Lightning Impulse Withstand Voltage
kV
95/110
Rated Frequency
Hz
50
Rated Short-Time Withstand Current (4s)
kA
40
Rated Peak Withstand Current
kA
100
Protection Level: Gas Tank/Cabinet
IP67/IP42
Rated Operating Pressure (Gauge Pressure at 20℃)
MPa
0.02
Minimum Operating Pressure (Gauge Pressure at 20℃)
MPa
0.01
Insulating Gas
SF6
Overall Dimensions [Width * Depth * Height]
mm
600 (800) * (1400 - 1820) * 2400